The reason:
(1)Insufficient air pressure;
(2)Loose knife button poor contact or line break;
(3)Loose knife button PLC input address point burned out or no signal source;
(4)Loose knife relay does not operate;
(5)Loose knife solenoid valve is damaged;
(6)The amount of cutting is insufficient;
(7)The knife cylinder cup is short of oil;
(8)The punching cylinder is faulty.
Countermeasures:
(1)Check the air pressure until the air pressure reaches 6 kg plus or minus 1 kg;
(2)Replace the switch or check the line;
(3)Replace the PLC input port on the 1/0 board or check the PLC input signal source and modify the PLC program;
(4)Check whether the PLC output signal is/is not, whether the PLC output outlet is burned out, modify the PLC program;
(5)If the solenoid valve coil is burned out, replace the solenoid valve coil, the solenoid valve body leaks, the piston does not move, then replace the valve body;
(6)Adjust the cutting amount to loosen the knife smoothly;
(7)Add the hydraulic oil in the tool cylinder oil cup;
(8)The internal screw of the punching cylinder is loose and leaking, then the screw should be re-tightened and the sealing ring in the cylinder body should be replaced;
(9)If it cannot be repaired, replace the punching cylinder.
We use cookies to enable all functionalities for best performance during your visit and to improve our services by giving us some insight into how the website is being used. Continued use of our website without having changed your browser settings confirms your acceptance of these cookies. For details please see our privacy policy.